15mm and 22mm thermostatic mixing valve is primarily designed for single outlet use. Featuring a fail safe operation and are approved to TMV2, TMV3 and WRAS
TECHNICAL SPECIFICATIONS:
Temperature setting range: 38 to 46°c
Accuracy: ±2°C
Max. working pressure (static): 10 bar
Max. working pressure (dynamic): 5 bar
Max. inlet temperature: 100°C
Max. inlet pressure ratio (H/C or C/H): 2:1
Minimum temperature difference between the inlet hot water and the outlet mixed water to ensure anti-scald performance : 10°C
Minimum flow rate for stable operation: 3.7l/min
POS carton with full instructions.
ADVMV00015 15mm Mixing Valve
ADVMV00022 22mm Mixing Valve